Add to Cart
Falling Film Type Tube Heat Exchanger
Water Cooling Evaporator
Falling Film Type Tube Heat Exchanger Water Cooling Evaporator is applicable to water units, water
source heat pump units, etc.
Suitable refrigerants of R22, everything,, R407C, R410A, etc.
Apply load cold agent for tap water, underground water, river water and sea water or brine, water and
glycol solution, sulfate solution, etc.
For heat exchange tube, copper
pipe, copper nickel alloy tube, aluminum brass tube, stainless steel tube,
etc. Shell using seamless steel pipe, stainless steel tube, etc.
1, Heat exchange tube: there are two main specifications.
(1) ∅ within 5/8 "efficient copper pipe outside screw wing, ∅ 5/8" stainless steel pipe.
(2) the ∅ 3/4 "inside outside screw wing efficient copper tube, ∅ 3/4" stainless steel pipe
Falling film type shell and tube heat exchanger water-cooled evaporator
Falling film type shell and tube heat exchanger water-cooled condenser
EVAPORATOR (SINGLE CIRCUIT)
CAPACITY: 120KW TO 270KW
Models | QXU120S8 | QXU135S8 | QXU155S8 | QXU185S10 | QXU220S10 | QXU270S10 | ||
Rated data Refrigerant R22 ti=12°C te=2°C tu=7°C Dts=5°C | Qn | KW | 120 | 135 | 155 | 185 | 220 | 270 |
Kcal/h(×103 ) | 103.2 | 116 | 133.3 | 159 | 180 | 232 | ||
Wn | m3 /h | 20.3 | 23.2 | 26.7 | 31.8 | 37.8 | 46.4 | |
Wm | m3 /h | 25 | 28 | 30 | 41 | 43 | 65 | |
Dpn | bar | 0.41 | 0.44 | 0.37 | 0.36 | 0.43 | 0.42 |
Models | QXU120S8 | QXU135S8 | QXU155S8 | QXU185S10 | QXU220S10 | QXU270S10 | |
Dimension(mm) | A | 1815 | 2115 | 2315 | 2320 | 2654 | 2654 |
B | 219 | 219 | 219 | 273 | 273 | 273 | |
C | 180 | 180 | 180 | 200 | 234 | 234 | |
D | 1530 | 1830 | 2030 | 2000 | 2280 | 2280 | |
E | 240 | 240 | 240 | 300 | 300 | 300 | |
Vent | S1 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 |
Outlet | S2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 | 1/2 |
Connection | W(DN) | 80 | 80 | 80 | 100 | 100 | 100 |
D1(mm) | 35 | 35 | 35 | 35 | 35 | 35 | |
D2(mm) | 54 | 54 | 67 | 67 | 80 | 80 | |
P(kg) | 145 | 155 | 163 | 232 | 279 | 289 | |
Qn-rated refrigerating capacity Wn-cooling water flow Wm-maximum cooling water flow Dpn-pressure drop of recirculating cooling water Dts-overheat temperature |
CONDENSER SERIES SINGLE CIRCUIT
CAPACITY: 220RT TO 426RT
Model | Refrig. ton (RT) | Refrig. ton (104kcal/h) | Dimension (mm) | Weight (kg) | Max. water flow | |||||||
D | T1 | T | A | C | E | H1 | H2 | |||||
QXC220S16A | 220 | 78.55 | 426 | 2860 | 3326 | 150 | 530 | 260 | 310 | 310 | 730 | 165.8 |
QXC240S16A | 240 | 81.65 | 426 | 2860 | 3326 | 150 | 530 | 260 | 310 | 310 | 763 | 181 |
QXC260S20A | 260 | 84.36 | 480 | 3200 | 3666 | 150 | 530 | 280 | 310 | 310 | 802 | 195.5 |
QXC280S20A | 280 | 88.24 | 480 | 3200 | 3666 | 150 | 530 | 280 | 400 | 290 | 841 | 211 |
QXC320S20A | 320 | 95.21 | 480 | 3200 | 3666 | 150 | 600 | 280 | 400 | 290 | 912 | 240.6 |
QXC340S22A | 340 | 98.68 | 530 | 3500 | 3966 | 150 | 600 | 300 | 400 | 290 | 963 | 256 |
QXC380S22A | 380 | 106.53 | 530 | 3500 | 3966 | 150 | 650 | 300 | 400 | 290 | 1015 | 285.5 |
QXC426S22A | 426 | 115.62 | 530 | 3800 | 4266 | 150 | 650 | 300 | 400 | 290 | 1088 | 320 |
Model | S (Vent) | P (fluoride inlet) Copper pipe diameter (inch) | L(fluoride outlet) Copper pipe diameter (inch) | W (standard port) | W (optional port) |
FPT(inner pipe thread) | Male flange | Male flange | |||
QXC220S16A | 3/8 | 3-1/8 | 1-5/8 | DN125 | DN125 |
QXC240S16A | 3/8 | 3-1/8 | 1-5/8 | DN125 | DN125 |
QXC260S20A | 3/8 | 3-1/8 | 1-5/8 | DN125 | DN125 |
QXC280S20A | 3/8 | 4-1/8 | 2-1/8 | DN150 | DN150 |
QXC320S20A | 3/8 | 4-1/8 | 2-1/8 | DN150 | DN150 |
QXC340S22A | 3/8 | 4-1/8 | 2-1/8 | DN150 | DN200 |
QXC380S22A | 3/8 | 4-1/8 | 2-5/8 | DN200 | DN250 |
QXC426S22A | 3/8 | 4-1/8 | 2-5/8 | DN200 | DN250 |